ENGINE GENERATOR INTEGRATED SWITCHGEAR
SPECIFICATIONS
ConfigurationFloor Standing modular switchgear paralleling system (Master Breaker Panel for the first 2 gensets, separate structures for up to 8 additional gensets , utility, and load control/distribution)
Modes of OperationEmergency Standby with redundant master control. Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
ApplicationLV only (208V - 480V)


technical summary
ConfigurationFloor Standing modular switchgear paralleling system (Master Breaker Panel for the first 2 gensets, separate structures for up to 8 additional gensets , utility, and load control/distribution)
Modes of OperationEmergency Standby with redundant master control. Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
ApplicationLV only (208V - 480V)


generator protective devices
ANSI Protective Devices15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)
utility protective devices
ANSI Protective Devices(Utility Grade) SR-750 / SEL-351S, 25, 27/59, 81 O/U, 32,47 (Industrial Grade) 15
environmental parameters
CertificationsUL891
Control Panel EnclosureNEMA1
Operating Temperature0°C to 55°C
Storage Temperature-20°C to 60°C
Engine Generator Integrated Switchgear (EGIS) STANDARD EQUIPMENT
- master breaker panel mbp for first 2 gensets
With electrically operated generator circuit breakers, lugs or cross-bus, and genset controls - 12" graphical color touchscreen display hmi instant auto selector switch
Allows user to return system to automatic in the event of a touchscreen failure - spare inputs and outputs
2 discrete inputs and 3 discrete outputs programmable from the HMI - audible alarm
Horn Silence Button
Emergency Stop Button for Each generator Top or Bottom Conduit Access (for MCP) for interconnect control wiring access
Engine Generator Integrated Switchgear (EGIS) OPTIONS
- generator breaker panel for 1 or 2 incremental gensets up to 8 additional gensets
With breaker position indications, circuit breaker control switch, generator controller, and user programmable logic I/O - utility breaker panel
With closed transition soft transfer and utility control for 1 LV circuit breaker, utility grade protective relay, utility close lockout switch, breaker position indications, and circuit breaker control switch - supplemental hardware synchronization check relay ansi 25 device
Provides additional discrete synchronization protection - data table interface
Accomodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP - generator demand priority control
Automatically match the on-line generator capacity to the loads, and avoid unnecessary operation of generator sets. - distribution breaker panel slave
With I/O module for control of up to 3 circuit breakers
Each slave panel contains 3 distribution breakers