CAT XLM SWITCHGEAR
SPECIFICATIONS
ConfigurationTraditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
Modes of OperationEmergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
ApplicationLV and MV ( 208V - 38 kV


technical summary
ConfigurationTraditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
Modes of OperationEmergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
ApplicationLV and MV ( 208V - 38 kV


generator protective devices
ANSI Protective Devices15/25, 27/59, 81 O/U, 32, 40, 50, 51
utility protective devices
ANSI Protective Devices15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86
environmental parameters
CertificationsIBS, CBC, UBC
oshpd certified
Environmental ParametersControl Panel Enclosure
nema 1 or nema 3r freestanding construction
Environmental ParametersOperating Temperature
0 degrees to 50 degrees c
Environmental ParametersStorage Temperature
20 degrees c to +60 degrees c
Environmental ParametersLow Voltage Standards
nema sg5 csa ansi c3751 ansi c37201 ul 1558 or ul 891 nfpa 110 nfpa 99 and nfpa 70
Environmental ParametersMedium Voltage Standards
nema sg5 ansi ieee c37202 csac222 no 31m89 eemac g832 nfpa 70 nfpa 99 and nfpa 1110
Cat XLM Switchgear STANDARD EQUIPMENT
- choice of 19” surface acoustic wave color or 15” resistive color touchscreen
- user selected multifunction relay utility grade
- circuit breaker control switch withindicators
- audible alarm
Horn Silence Button
Emergency Stop Button for eachgenerator
Instant Auto Switch to Return System to Ready State
Generator Demand Priority Control- automatically match the online generator capacity to the loads and avoid unnecessary operation of generator sets
Cat XLM Switchgear OPTIONS
- redundant touchscreens
- redundant communication networks
- ats and ups communication
Display
Data Table Interface- accommodates interface with a building management system for monitoring all system parameters via modbus rtu or tcp
Historical Trending (19” Touchscreen)
Remote Event Notification
Utility Interconnect Multi-function Relay (Utility Grade)
Supplemental Hardware Synchronization check relay (ANSI 25 Device)- provides additional discrete synchronization protection
Remote Power Monitoring System - to monitor breaker status alarms metering and other operating parameters
Distribution Breaker monitoring and control NFPA Compliant JCAHO Reporting
Long Term Historical Trending