CAT EGP SWITCHGEAR
SPECIFICATIONS
ConfigurationTraditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
Modes of OperationMulti-unit Island and multi-unit standby mode with optional redundant controls and components.
ApplicationLV and MV (208V - 38 kV)


technical summary
ConfigurationTraditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
Modes of OperationMulti-unit Island and multi-unit standby mode with optional redundant controls and components.
ApplicationLV and MV (208V - 38 kV)


generator protective devices
ANSI Protective Devices15/25, 27/59, 81 O/U, 32, 40, 50, 51
environmental parameters
CertificationsIBC, CBC, UBC
oshpd certified
Environmental ParametersControl Panel Enclosure
nema 1 or nema 3r freestanding construction
Environmental ParametersOperating Temperature
0°c to 50°c
Environmental ParametersStorage Temperature
20°c to +60°c
Environmental ParametersLow Voltage Standards
nema sg5 csa ansi c3751 ansi c37201 ul 1558 or ul 891 nfpa 110 nfpa 99 and nfpa 70
Environmental ParametersMedium Voltage Standards
nema sg5 ansi ieee c37202 csac222 no 31m89 eemac g832 nfpa 70 nfpa 99 and nfpa 1110
Cat EGP Switchgear STANDARD EQUIPMENT
- egp switchgear
Choice of 19” Surface Acoustic Wave Color or 15” Resistive Color Touchscreen
Circuit Breaker Control Switch with Indicators
Audible Alarm - horn silence button###emergency stop button for eachgenerator###instant auto switch###generator demand priority control
Cat EGP Switchgear OPTIONS
- redundant touchscreens
- redundant communication networks
- ats and ups communication
Display
Data Table Interface- * accomodates interface with a building management system for monitoring all system parameters via modbus rtu or tcp
Historical Trending (19” Touchscreen)
Remote Event Notification
Supplemental Hardware Synchronization check relay (ANSI 25 Device)- * provides additional discrete synchronization protection
Remote Power Monitoring System - * to monitor breaker status alarms metering and other operating parameters
Distribution Breaker monitoring and control NFPA JCAHO Reporting
Long Term Historical Trending