XQC1600
SPECIFICATIONS
IPP Rated 50Hz1515 kW (1893 kVA)
IPP Rated 60Hz 1705 kW (2131 kVA)
IPP Overload 50Hz1590 kW (1987 kVA)


generator
IPP Rated 50Hz1515 kW (1893 kVA)
IPP Rated 60Hz 1705 kW (2131 kVA)
IPP Overload 50Hz1590 kW (1987 kVA)
IPP Overload 60Hz1790 kW (2237 kVA)
Voltage400 - 480 V
Frequency50/60 Hz


engine
EngineCAT 3516C-HD DIESEL ENGINE
FuelDiesel
dimensions
Width (w/o Chassis)2438 mm
Height (w/o Chassis)2896 mm
Length (w/o Chassis)12192 mm
Weight (w/o Chassis) (w/ fuel, lube oil and coolant)31818 kg
XQC1600 STANDARD EQUIPMENT
- cat 3516chd heavy duty diesel engine
Heavy duty, dual element, PowerCore air cleaners with service indicators
Triple, primary fuel filters with water separators and bypass valves for on-the-fly filters changes
Secondary fuel filters on engine
Full flow oil filters with water-cooled oil cooler. Requires API CI-4 or higher lube oil.
Lubricating oil system includes make-up system (113-L tank), oil drain lines routed to the engine rail, and quick evacuation system for faster, cleaner oil changes
Jacket water heater (9 kW, 3-phase 480VAC) with electric pump
Fuel cooler and electric fuel priming pump
Electronic differential pressure monitoring of all filters
Electronic ADEM™ A4 engine controls
Dual 24V electric starting motors - sr5 generator
Double-bearing, 1844-frame, SR-5 generator with anti-condensation space heaters (1.2 kW, 480V)
Brushless, form-wound, permanent magnet excited, three-phase, 4-lead design
Class H insulation operating at Class F temperature for extended life
Cat Integrated Voltage Regulator (Cat IVR)
Stator winding and bearing temperature detectors monitored by RTD module
Metallic mesh generator air inlet filters (2)
System 4 insulation protection - 40 iso high cube container
9-High stackable, CSC certified
Sound attenuated, hinged, radiator intake louvers
Sound attenuated package air intake louvers with foldable awnings
Five (5) lockable personnel doors with panic releases
Interior walls and ceilings insulated with 100 mm of acoustic paneling
Side bus bar access door with external access load cable connections
Shore power via distribution block connections for jacket water heater, battery charger, space heaters, and generator anti-condensation heaters
Six (6) DC lights with 60-min timer
Single-wall, 946-L (250gal) fuel tank; certified to BS799-5
Solenoid fuel fill control valve for automated filling
Sound attenuated to 75 dB(A) (50Hz) 81 dB(A) (60Hz) at 7m (23 ft)
Four (4) 1400-CCA, Group 4D, maintenance-free batteries, and 50A battery charger
Insulated exhaust silencer with 1.8-m (6ft) stainless steel exhaust stack for increased site power density
Engine vibration isolators
Easy drain access to standard fluids
Standard Cat decals (Optional) and painted Cat Power Module White - cooling
Cooling package provides 49°C (120°F) ambient capability (50 - 60 hz at ipp ratings @ 750m 2460 ft###vertical nonstacked radiator cores with dimpled fins and vertical air discharge###variable frequency fan drive with smart fan control###cat extended life coolant
Generator Controls and Protection - emcp 43 generator set controller###automatic startstop with cool down timer###generator protection features 25 32 40 5051 2759 81 ou###agc4 provides voltage and frequency adjust base load pf load sharing synchronizer auto start stop control
generator CB control, SCADA Interface (Ethernet), fuel level indications - alarms fuel tank fuel transfer control###reverse compatibility for interface to legacy power modules###100 kaic 4000aframe generator circuit breaker with lsig trip unit###multimode operation island kwkvar sharing auto mains failure peak shaving base load power export zero power transfer power management with multiple units###manual and automatic paralleling capability###metering display voltage current frequency power factor kw whm kvar and synchroscope
Quality - factory testing of complete power module###ce certified nema iso and ieee standards###o