XQ2000
SPECIFICATIONS
Continuous Rating1400 ekW (1750 kVA)
Prime Rating1600 ekW (2000 kVA)
Voltage400/240 V


BENEFITS AND FEATURES
generator
Continuous Rating1400 ekW (1750 kVA)
Prime Rating1600 ekW (2000 kVA)
Voltage400/240 V
Frequency50 Hz
Frame Size826
Pitch0.6667
No. of poles4
ExcitationStatic regulated brushless PM excited
ConstructionsDouble bearing, close coupled
InsulationClass H
EnclosureDrip proof IP22
AlignmentPilot shaft
Overspeed capability – % of rated125% of rated
Voltage regulator3 phase sensing with Volts-per-Hertz
Voltage regulationLess than ± 0.5% voltage gain; Adjustable to compensate for engine speed droop and line loss
Wave form deviationLess than 5% deviation
Telephone Influence Factor (TIF)Less than 50
Harmonic Distortion (THD)Less than 5%


engine
CAT 3516B Flex-Fuel Engine3516B, 4-Stroke diesel
Bore170 mm
Stroke190 mm
Displacement69 L
Compression ratio15:1
AspirationTA
Fuel systemEUI
Governor typeCat ADEM A4 Control System
EmissionsNon-Certified
dimension
Width (without Chassis / with Chassis)2438 mm
Height (without Chassis)2896 mm
Height (w/Chassis)4267 mm
Length (without Chassis / with Chassis)12192 mm
Weight (without Chassis) (w/lube oil and coolant)29021 kg
Weight (w/Chassis) (w/lube oil and coolant)33638 kg
BENEFITS AND FEATURES
XQ2000 - DGB STANDARD EQUIPMENT
- engine
Cat 3516B heavy duty flex fuel engine
Heavy duty, single element canister type air cleaner with service indicator
Fuel filters – primary and duplex secondary with integral water separator and change-over valve
Spin on, full flow oil filters with water cooled oil cooler. Requires API CF-4 lube oil
Stainless Steel Aftercooler core
Jacket water heater, 9kW, 400V, 50 Hz, 3-phase w/isolation valves
Fuel cooler and priming pump
Electronic ADEM™ A4 controls
Integrated Sensor Module (ISM) for combustion sensing and exhaust gas sensing
Dual 24V electric starting motors - generator
Double bearing SR-4B brushless, form wound, permanent magnet excited, three-phase with Cat digital voltage regulator (Cat DVR), space heater, 6-lead design, Class H insulation operating at Class F temperature for extended life, winding temperature detectors and anti-condensation space heaters (120/240V 1.2 kW).
Generator equipped with System 4 insulation protection. - containerized module
40' ISO high cube container, 9-High stack CSC certified
Four (4) sound attenuated air intake louvers and 3 lockable personnel doors with panic release
Interior walls and ceilings insulated with 100 mm of acoustic paneling
Floor of container insulated with acoustic glass and covered with galvanized steel
Side bus bar access door, external access load connection bus bars
Shore power connection via distribution block connections for jacket water heater, battery charger, space heaters, and generator condensate heaters
Six (6) DC lights
1,250 gal fuel tank, UL listed, double wall, >13 hr runtime @ Continuous rating
Solenoid diesel fuel fill control valve
Lube oil level regulator with makeup tank
Sound attenuated 75 dB(A) @ 15 m (50 ft)
Four (4) oversized maintenance-free batteries, battery rack and 20-Amp battery charger
Critical grade exhaust silencer with dual 2 m (6.5 ft.) exhaust stacks for increased site power density
Vibration isolators, stainless steel fastening hardware and hinges
External drain access to standard fluids
One 4.5 kg (10lb) carbon dioxide fire extinguisher
Standard Cat rental decals and painted standard Cat power module white
110% spill containment system for on-board engine fluids
Methane Leak Detection - gaseous fuel system
Low pressure regulator
Electronically actuated fuel control valve
Gaseous fuel heater
Electronically controlled gas shut-off valve
Gas induction nozzles
1 micron gas fuel filter with dP sensors and isolation ball valve with 1” BSP drain plug for fluid build-up
CSA certified gas electronic components - cooling
Standard cooling provides 43C (110F) ambient capability at 100% Prime
Horizontally mounted radiator with vertical air discharge
Variable frequency fan drive (VFD) for optimal partial load fuel consumption - generator controls and protection
Controls provide auto paralleling AGC-4 controller, voltage and frequency adjust, base load / PF / load sharing / synchronizer, auto start / stop control - generator cb control scada interface ethernet fuel level indications
alarms, fuel tank fuel transfer control
EMCP 4.3 genset mounted controller
Automatic start/stop with cool down timer
Generator Protection features: 25, 32, 40, 50/51, 27/59, 81 O/U
Reverse compatibility for interface to legacy power modules
3000A UL rated generator circuit breaker with LSIG trip unit w/ammeter
Multi-mode operation (island, multi-island and utility parallel), load sharing (multi-unit only)
Manual and automatic paralleling capability
Metering display: voltage, current, frequency, power factor, kW, WHM, kVAR, and synchroscope - quality
Factory testing of standard generator set and complete power module
UL, NEMA, ISO and IEEE standards
O - m manuals
EMCP 4.3 Local Control Panel - generator mounted emcp 43 provides power metering protective relaying and engine and generator control and monitoring###convenient service access for cat service tools not included###integration with the cat dvr provides enhanced system monitoring###ability to view and reset diagnostics of all controls networked on j1939 datalink eliminates need for separate service tools for troubleshooting###realtime clock allows for date and timestamping of diagnostics and events###customer communication through modbus tcp###true rms ac metering 3 phase ll volts ln volts phase amps hz ekw kva kvar kwhr % kw pf
EMCP 4.3 Engine Operator Interface - graphical display with positive image transflective lcd adjustable white backlightcontrast###digital indication for
- rpm
- dc volts
- operating hours
- oil pressure
- coolant temperature
- oil temperature
- gas pressure
- gas substitution %
- gas shutoff valve status
- dgb activation
- ###two led status indicators 1 red 1 amber###engine cooldown timer###engine cycle crank###three engine control keys and status indicators runautostop###lamp test and alarm acknowledgement keys###warningsshutdowns with indicating text for
- low oil pressure
- overspeed
- high oil temperature
- overcrank
- emergency stop
- agc4
- ###emergency stop pushbutton###display navigation keys including two shortcut keys for engine parameters or generator parameters
Container - 40’ iso high cube container csc 9high stack certified###painted standard cat power module white per caterpillar specifications###standard air intake louvers###three 3 lockable personnel doors with panic release###fire extinguisher###110% spill containment system for onboard engine fluids
AGC-4/EMCP 4.3 Protective Relaying - generator protective features
- 25 synccheck agc4
- 32 rev power emcp 43 and agc4
- 40 loss of excitation cat dvr and agc4 impedance based
- 5051 inst and time overcurrent gcb trip unit and agc4
- 47 negative voltage sequence agc4
- 46 negative sequence current agc4
- 2759 phase underover voltage emcp 43 and agc4
- 81ou underover frequency emcp 43 and agc4
- ###package mounted agc4 controls provides auto paralleling canbus ethernet communications pwm and analog outputs and legacy analog load sharing real and reactive ###agc4 main display aop secondary display
Voltage Regulation and Power Factor Control Circuitry - generator mounted automatic voltage regulator microprocessor based###manual raiselower voltage adjust capability and varpower factor control circuitry all via agc 4 for maintaining constant generator power factor while paralleled with utility###includes rfi suppression exciter limiter and exciter diode monitoring
Current Transformers - ct’s rated 30005 with secondaries wired to shorting terminal strips
Circuit Breaker - 3000a fixed type 3 poles genset mounted electrically operated insulated ul489 cb###solid state trip unit for overload time overcurrent and fault instantaneous overcurrent protection lsig is standard###includes dc shunt trip coil activated on any monitored engine or electrical fault 100 kainterrupting capacity at 480 vac###undervoltage release 24vdc###optional external ground fault sensingtrip requires additional ground ct
Internal Lighting - six 6 internal 24vdc led lights with timers located at the control area personnel door###one 1 duplex service receptacle
Battery Charger and Batteries - 24 vdc20a battery charger with floatequalize modes and charging ammeter###four oversized maintenance free batteries
Emergency Stop Pushbutton - single emergency stop pushbuttons esp located on rear face of generator set controls area###emergency stop pushbutton located on the container exterior at each personnel door3
Exhaust Silencer - critical grade internally mounted dual cylindrical exhaust silencers###2 m high vertical discharging exhaust stack located in radiator discharge area
Fuel Tank - ul listed 1250 gallon double walled tank###fuel solenoid valve system###triple fuelwater separators
Modes of Operation - provides for single unit standalone operation island mode paralleling and load sharing with other power modules and single unittoutility mode paralleling for base load control with open transition between paralleling modes*###island mode paralleling features
- agc4 control allows single unit to connect to a dead bus
- auto synchronization voltage
phase matching) - Load sharing (kW) analog signal (like units
- legacy compatible
- load sharing kvar analog signal like units only
- ###utility mode paralleling features
- auto synchronization voltage
phase matching) - Base-load control (selectable: programmable set-point or potentiometer adjust)
- Soft load/unload (programmable, shared setpoint)
- Power Factor control (programmable setpoint)
Three phase, plus full rated neutral, bus bars are tin-plated copper with NEMA standard hole pattern for connection of customer load cables and generator cables.
Bus bars are sized for full load capacity of the generator set at 0.8 power factor.
Includes ground bus, tin-plated copper, for connection to the generator frame ground and field ground cable.
3 phase, 400VAC, 50 Hz, 50 amp input which can be derived from either the Power Module main output bus (Internal) or customer supplied shore power (External) via selector switch.
Onboard 50 Hz Transformer for the Power Module AC auxiliaries provides 240/120 VAC for all module accessories except Jacket water heater (400V). Includes controls to de-energize jacket water heaters and generator space heater when the engine is running
Includes oil pan-mounted oil level regulator and 114 L (30 gal) oil tank for maintaining oil pan levels in extended run applications. Oil tank can be remotely filled without shutting down the engine.
XQ2000 - DGB OPTIONS
- trailer
Three axle with Anti-lock brake system
Goodyear G314 295/75R225 Load Range G
MOTEUR
- Generator set manufactured in ISO 9001:2000 compliant facility
- Package factory designed and production tested
- Generator set and components meet or exceed the following specifications: AS1359, AS2789, BS4999, DIN6271, DIN6280, EGSA101P, JEM1359, IEC 34/1, ISO3046/1, ISO8528, NEMA MG1-22
BENEFITS AND FEATURES
- Cat® dealers provide extensive post sale support including maintenance and repair agreements
- Supported 100% by your Cat dealer with warranty on parts and labor
BENEFITS AND FEATURES
- The compact, four-stroke-cycle Cat 3516B turbocharged-aftercooled diesel engine combines durability while providing dependability and economy
- Stainless steel engine aftercooler core to extend component, oil, and overall engine life when using gaseous fuels with elevated H2S levels
- Fuel system operates on a variety of gaseous fuels
- Integral gas train, gas filter, and isolation valve
- Includes methane detection system and related safeties
BENEFITS AND FEATURES
Cat SR4B 826 frame generator designed to match the performance and output characteristics of the Cat diesel engine
Double bearing, wye-connected, static regulated, brushless, permanent magnet excited
BENEFITS AND FEATURES
- 110% spill containment of onboard engine fluids
- Positive crankcase fumes ventilation
BENEFITS AND FEATURES
- Provides 9-high stack CSC rated enclosure for ease of transportation and protection
- Meets 75 dB(A) at 15 meters or below per SAE J1074 measurement procedure at prime rating
BENEFITS AND FEATURES
- Requires gas inlet pressure range of 5-35 psi (34-241 kPa)
- Achieves up to 70% substitution, depending on gas quality, while maintaining diesel performance and safe engine operation
- Closed loop control system enables maximum substitution over the widest load range in the industry
- Maintains traditional diesel generator set power and transient response performance
- DGB system, when enabled, can automatically activate when gas supply is detected
- Accepts a wide range of gas quality and automatically adjusts to fuel quality changes, eliminating the need for field calibration
- Leverages current hardware from G3516 product line while minimizing changes to core diesel engine
- Fully integrated diesel and gas controls into single engine control unit with single point operation for generator set and DGB system
BENEFITS AND FEATURES
- Horizontally mounted radiator with vertical discharge with high efficiency fan
- Provides 43C (110F) ambient capability
- Variable frequency drive fan controls improve partial load fuel consumption
BENEFITS AND FEATURES
- Provides auto paralleling using package mounted controls
- EMCP 4.3 offers engine and generator monitoring and protection, including DGB enable and substitution level set points
- AGC-4 provides paralleling, load sharing, VFD control, and primary generator protection
BENEFITS AND FEATURES
- 3 phase sensing and adjustable V/Hz regulation
- Provides precise control, excellent block loading, and constant voltage in the normal operating range