ATC POWER BREAKER BYPASS ISOLATION OPEN/CLOSED TRANSITION AUTOMATIC TRANSFER SWITCH
Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a compact package. A Bypass Isolation Automatic Transfer Switch (ATS) provides fully functioning transfer in applications where emergency power to critical loads must be maintained at all times with no interruption. This type of design allows for inspection, maintenance or replacement of the power switching mechanisms with no interruption in electrical service. Breaker based Bypass isolation ATS are available from 200A to 5,000A.
SPECIFICATIONS
Rating Range200-5000A
Transfer TypeBypass isolation, Closed transition
Switch TypePower Breaker


technical summary
Rating Range200-5000A
Transfer TypeBypass isolation, Closed transition
Switch TypePower Breaker


ratings
Control Power200-5000A, 2-, 3-, 4-pole
100% rated Short
System Voltage Application120-600 Vac 50/60 Hz
Time Withstand85,000 for 30 cycles
Withstand100 kAIC at 600V, 3 cycles
Applicable TestingCSA C22.2 No. 178 certified
UL 1008 listed up to 3200A
4000A, and 5000A UL 891 listed
ATC Power Breaker Bypass Isolation Open/Closed Transition ATS STANDARD EQUIPMENT
- controls and wiring
All controls relays and industrial grade relays are totally encapsulated to minimize exposure to dust and dirt. Lugs are 90º rated and all control wire is #16 AWG, type XLPE with a 125º temperature rating. - enclosure
Durable powder-coated steel NEMA 1, 3R or 12 enclosures with three door hinges to ensure proper support of the door and door mounted devices. The hinges have removable hinge pins to facilitate door removal for easy wall mounting or service and are supplied with pad-lockable latches.
ATC Power Breaker Bypass Isolation Open/Closed Transition ATS OPTIONS
- available options
Integrated service entrance
Open or closed transition
Integral overcurrent protection
2- or 4-position test switch
Multi-meter options available
Selectable automatic or non-automatic operation
Space heaters
Load sequencing contacts
Surge suppression
Remote communications
Seismic Zone 4 Qualified (BOCA, CBC, IBC, UBC and OSHPD)
Field selectable, multi ratio, control voltage transformer 50/60 Hz - optional delayed transition includes
Time delay neutral
In-phase transition
Pre-transfer signal with 1 N.O. and 1 N.C. contacts